Call Now!
888-917-8777
Smoke curtains Fire curtains
Most fire codes  depend upon the National Fire Protection Association guidebooks.  In turn these propose the use of simple zone models that solve conservation of mass and energy in a control-volume sense for each zone. One weakness of zone modeling is that momentum conservation is only captured through use of loss coefficient at openings. The strength of zone models is that they are very fast compared with computational fluid mechanics (CFD) based models. Multi-level Atriums are examples of large spaces for which these conventional zone-model approaches are not always effective. CFD, sometimes called “field-modeling” in the fire community to distinguish it form zone-modeling, has an unparalleled potential as an engineering estimator of fire consequence in atria since it permits specification of momentum conservation as well as much finer spatial and temporal resolution. Fire physics is the key to the approach. In addition, CFD approaches provide a link between outside building weather conditions and fire and smoke development. In large-volume spaces such atria, smoke management systems are often an important aspect of fire protection, with their primary goal being to ensure that the impact of smoke and heat on occupants is not life threatening (NFPA 92B). This involves keeping the height of the smoke layer above the highest level of occupancy for a defined period, longer than the expected time to evacuate the building. Atrium smoke management relies on the buoyancy of hot smoke rising above a fire. As it rises, relatively cool ambient air is entrained into the plume decreasing the temperature and increasing the mass flow rate of contaminated air. Upon reaching the ceiling, the momentum of the plume is diverted into a jet which spreads the smoke over the ceiling area. Long travel distances and architectural features can cause further entrainmen tof air, adding to the smoke filled volume. Once the ceiling jet has covered the ceiling, the depth of the smoke layer increases until either the atrium fills with smoke or the rate of smoke entry into the layer is balanced bythe rate of exhaust. Make-up air must be introduced below the smoke layer and should not generate turbulence in the vicinity of the plume or smoke layer, since this would tend to increase the  required exhaust rate. This often means that make-up air should be provided from a wide distribution of supply points over the lower levels of the building to keep air speeds below 200 feet per minute within the atrium. In some situations, make-up air can be used to provide a degree of protection for egress routes. The design of an effective smoke management system requires calculation of smoke mass flow rates and rate of descent of the smoke layer. It is particularly important to consider the time from ignition of the fire until detection, after which the system would be expected to control further growth of the smoke layer. A starting point to estimate quantities of smoke from a fire is the empirical formulae listed in applicable building or fire codes, or the NFPA 92B.
 
BLE SD series smoke curtains are the gold standard of the smoke curtain technology. Underwriters Laboratories listed, patent pending technology which provides an automatic gravity fail-safe smoke barrier invisible under non-fire conditons. In a fire scenario, the U.L. listed smoke curtains deploy by a signal form the fire alarm system or loss of power or communication from the fire alarm system simulating fail-safe and provide a physical barrier to smoke and compartmentalize or datum  the smoke by reducing horizontal smoke and fire migration. Desgined to develop datums six feet  eight inches or six feet above the finished floor. This allows for more freedom of design for architects to draw more ambitious and unique atriums open to above and below on multiple levels while still complying with the IBC. Smoke  draft curtains are designed to develop datums six feet above egress-able horizontal  walking surfaces and hold the boyant smoke layer of smoke for calculated amounts of time, allowing for occupants' safe egress to the accessible exits. Life safety joined with design—a winning combination for all. This mitigates the requirement for mechanically supplied make-up air for an atrium smoke exhaust system. Typically, we have been able to reduce exhaust requirements in half by use of curtain technology (see case studies) thus reducing the need for larger volumes of make up air. Mechanically supplied make up air for an atrium design fire is expensive and not fail safe. 
 
Multi-level atriums are a perfect example for the BLE SD series smoke curtains.  CFD modeling is required to locate the smoke curtains in communicating spaces of a multi-level atrium. The smoke curtain is designed to work in conjunction with pressurization differeneces creating an air seal and is considered a deployable smoke barrier. Smoke seal curtains can be utilized as atrium separations in multi-level atriums utilzing air exhaust as the seal or overlaping walls. Headbox sizes are typically as small as 5.9 inches square for a typical ten foot drop and the mounting method is unistrut ceiling mount four foot on center with 3/8 threaded rods. Back mounts are also possible. The tubular motors are located inside the steel tubes and connect to motor control circuits that are run point to point in a low voltage loop from the group control panel to each motor control circuit and then back to the group control panel. If the electrical is run in this way then all up buttons on this loop would retract the curtains simultaneously. If independent modules to each up button is utlized and wired to each motor control circuit, then independent control of each curtain roller is achieved.
 
A smoke barrier conjunction with extraction pressurization differences are achieved. There are no limit switches and the stop is achieved by the bottom bar retractiing back iinto the bottom of the headbox. In addition, the curtain material is UL 10B time temperature curves, ASTME119  time temperature curves and listed under UL 10D  and can carry the UL label. Smoke Seal curtains achieved results BY air pressure differentials. Push-to-Exit buttons allow for easy retraction of the curtain when descended. Further, there is a two stage descent feature, delayed delayed descent feautures to keep curtain six foot eight inches A.F.F. An evacuation scenerio model must be undertaken to determine these guidelines by the fire protection engineer of record and authority having jurisdiction. At time of manufacturing, the two stage descent feature would be quantified as the options are one to nine minutes or thirty seconds to four and a half minutes in terms of delayed descent features. Any other time delays would be customized.
 
Fully automatic Smoke curtains are normally retracted in a steel head box, and descend by gravity during a fire condition, thus preventing the spread of smoke from one floor to another. Deployment is gravity fail-safe and does not require battery back-up to descend. Because our system control panel is UL 864 approved, it is able to tie into the building’s fire alarm panel and communicate that it is descending.  An evolution in building technology and is the gold standard for automatic deployable smoke barriers in compliance with NFPA92B for multi-level atriums and large spaces. Smoke curtains usually save the project money as their use limits the need for extraction and in many cases eliminates the need.
 
The SD series smoke draft curtain saves money and potentially is fail safe as the technology require no building power main or back up to deploy. Make up air is not fail safe and requires dedicated exhaust fans on back generator driven power supply. Curtain technology reduces the cubic feet per minute requirement of air required to supply to the atrium. When utilized in an atrium, the lobby doors are opened with pneumatic openers and the make up air is provided from outside air with no electrically powered supply air.What does this mean? Simply,  a chimeny effect  is created which channels the smoke along the Y- axis and creates a smoke partition with only a two inch shadow gap with no need for side guides for smoke protection. 
 
A unique small, compact, light weight product which is an evolution in building science. Underwriters Laboratories recognized this evolution and designed the designation under UL10D. It is due to the forward thinkers at UL, NFPA, AIA, SFPE and at BLE that continue to make advancements like these possible.Our vision is to continue to evolve, develop and improve and add value and approach each project with a  thoughtful approach as scientists, and specialists to protect public health, safety and general welfare as they relate to the construction and occupancy of buildings and structures. 
Installations for Multi-Level Atrium Smoke Control Systems
MIT, UMASS Integrated Sciences Building, Princeton Chemistry Building, PNC, Ground Zero Project, FIU
 
Installation Services
Rivet and CAD enabled design development, construction document review, shop drawings, verify in field shop drawings, full service installation, and coordination curtain system with fire alarm, electrical and air extraction companies, commissioning, smoke bomb testing and acceptance testing per adherence to NFPA 80 guidelines with the authority having jurisdiction.
 
Maintenance and Support
Maintenance contracts available for annual drop testing, 24 hour building services
 
References
UMASS - Click to download PDF
Turner Construction Company - Click to download PDF
 
footer